| Drawings issued for | Capstone example |
|---|---|
| Project number | CAP-01 |
| Model | |
| Address | (example) |
| City & province | Parry Sound, ON |
| Site / lot | |
| Postal code | |
| Dimensional information based on | Capstone plan |
| Attachment | Detached |
| Number of storeys | 1 + basement |
| Weather location | Parry Sound |
| Ventilation included? | Included |
| HRV? | Yes |
| Recovery % (sensible, at −25 °C) | 65% |
| Front facing | South ASSUMED |
| Air tightness | 3 ACH50, ELA 620 cm² @ 10 Pa ASSUMED |
| Wind exposure / shielding | AIM-2 site 7, walls 3, flue 3 |
| Internal shading | None in this calculation |
| Occupants | 4 |
| Units | Metric (SI) |
| Heating: outdoor temperature | -24 °C |
|---|---|
| Heating: indoor temperature | 22 °C |
| Mean soil temperature | 8 °C |
| Cooling: outdoor temperature | 28 °C |
| Cooling: indoor temperature | 24 °C |
| Latitude | 45.34° |
| Summer mean daily range | 14 °C or less |
| Above-grade walls | 2x6 @ 406, R22 batt + R5 ci (SB-12 A1, effective RSI 3.00) — U 0.333 |
| Below-grade walls | 200 mm concrete, R20 interior full height (BasementHLR BCIN_1) — U 0.269 |
| Floors | — |
| Ceilings | Attic, R60 blown — U 0.096 |
| Doors | Insulated steel — U 1.4 |
| Windows | Double low-e argon, U 1.6 — U 1.6, SHGC 0.4 |
| Skylights | — |
| Attached documents | Room-by-room results (this report) |
| Notes | Teaching example |
| Calculations performed by | Stephen Gilbert, SBG Design Works |
|---|---|
| Address | |
| BCIN |
| Item | W | BTU/h | Clause |
|---|---|---|---|
| Design heat loss, building (HLb) | 7,187 | 24,523 | 5.2.7 |
| of which ventilation at building level (HLvairb) | 483 | 1,648 | 5.2.3.2 |
| of which air leakage (HLairb) | 1,600 | 5,458 | 5.2.3.1 |
| Sensible heat gain, Σ HGsr | 3,584 | 12,229 | 6.2.9 |
| Nominal cooling capacity (CSCn = 1.3 × Σ HGsr) | 4,659 | 15,898 | 6.3.1 |
| Cooling capacity window, minimum | 3,728 | 12,718 | 6.3.2 |
| Cooling capacity window, maximum | 6,409 | 21,869 | 6.3.4 / 6.3.5 |
| 5.3.1 | MEETS Heating output 11254 W vs building loss 7187 W (≥ 100%) (157%) |
|---|---|
| 6.3.2–6.3.5 | MEETS Cooling 5275 W vs window 3728–6409 W (113%) |
| Room | Level | ΔT | Above-grade cond. | Below-grade | Level factor | Air change | Duct/pipe | Vent. | Total W | BTU/h |
|---|---|---|---|---|---|---|---|---|---|---|
| Living room | M | 46 | 942 | 0 | 0.4 | 176 | 0 | 0 | 1,118 | 3,814 |
| Kitchen / dining | M | 46 | 952 | 0 | 0.4 | 178 | 0 | 0 | 1,130 | 3,854 |
| Hall / stair | M | 46 | 154 | 0 | 0.4 | 29 | 0 | 0 | 183 | 625 |
| Primary bedroom | M | 46 | 544 | 0 | 0.4 | 102 | 0 | 0 | 646 | 2,204 |
| Bathroom | M | 46 | 161 | 0 | 0.4 | 30 | 0 | 0 | 192 | 654 |
| Bedroom 2 | M | 46 | 236 | 0 | 0.4 | 44 | 0 | 0 | 280 | 954 |
| Bedroom 3 | M | 46 | 441 | 0 | 0.4 | 82 | 0 | 0 | 523 | 1,784 |
| Basement (unfinished) | B | 46 | 321 | 1,353 | 0.6 | 960 | 0 | 0 | 2,634 | 8,988 |
| Σ rooms | 6,704 | 22,875 | ||||||||
| + ventilation, building level (5.2.7 note) | 483 | 1,648 | ||||||||
| HLb | 7,187 | 24,523 | ||||||||
| Room | Opaque | Glass cond. | Solar | People | Lights/appl. | Air leakage | Vent. | Duct | Total W |
|---|---|---|---|---|---|---|---|---|---|
| Living room | 73 | 40 | 551 | 140 | 0 | 8 | 36 | 0 | 848 |
| Kitchen / dining | 87 | 40 | 569 | 140 | 956 | 8 | 38 | 0 | 1,838 |
| Hall / stair | 38 | 0 | 0 | 0 | 0 | 0 | 2 | 0 | 40 |
| Primary bedroom | 45 | 19 | 204 | 0 | 0 | 3 | 15 | 0 | 286 |
| Bathroom | 17 | 3 | 20 | 0 | 0 | 0 | 2 | 0 | 43 |
| Bedroom 2 | 20 | 9 | 54 | 0 | 0 | 1 | 4 | 0 | 88 |
| Bedroom 3 | 35 | 16 | 177 | 0 | 0 | 3 | 12 | 0 | 243 |
| Basement (unfinished) | 37 | 10 | 139 | 0 | 0 | 2 | 10 | 0 | 198 |
| Σ HGsr | 3,584 | ||||||||
| Design temperature differences | Heating 46 K; cooling 4 K (5.1, 6.1.1) |
|---|---|
| Building volume Vb (inside dimensions) | 584 m³ |
| Gross floor area | 239 m² → lights/appliances 956 W (6.2.5) |
| Air leakage rates (AIM2.xls) | Heating 0.1788 ACH; cooling 0.0329 ACH — run 2026-10-23T21:14:39 ASSUMED |
| Air leakage note | ELA not measured: scaled from the tool's "Present (1961-)" type at the same volume (assumed) ASSUMED |
| AIM2.xls inputs | Station Parry Sound; site 7, wall shielding 3, flue shielding 3; highest ceiling 3.34 m; Detached, One, Full foundation; supply 25 L/s, exhaust 25 L/s |
| Foundation F1 (BasementHLR.xls) | BCIN_1 (#1); 12.2 × 9.8 m; height 2.44 m, depth 1.84 m; interior RSI 3.72, exterior RSI 0, slab RSI 0; soil 1, water table 2; windows 1.62 m² → 1,353 W |
| Ventilation | PVC 25 L/s; HRV sensible effectiveness 0.65; ATRE 0; into the central air system (not assigned to rooms) |
| Solar | Solar0 per 6.2.2.1; latitude factor 1.20 on S/SE/SW; shaded glass treated as north |
Prepared with the designer's own implementation of CSA F280-12; not software verified under F280-12 Clause 8. Spreadsheet-derived values are from CSA's AIM2.xls and BasementHLR.xls / SlabOnGradeHLR.xls run with the inputs above.