SAMPLE — teaching example house, not a client project. Back to SBG Design Works

Heat Loss and Gain Calculation — CSA F280-12

Capstone bungalow, Parry Sound · prepared 2026-10-24. Calculation method: CSA F280-12 Clauses 4–7. Air leakage rates from CSA AIM2.xls; foundation losses from CSA BasementHLR.xls / SlabOnGradeHLR.xls.

Heat loss and gain calculation summary sheet (Annex D)

Drawings issued forCapstone example
Project numberCAP-01
Model
Address(example)
City & provinceParry Sound, ON
Site / lot
Postal code
Dimensional information based onCapstone plan
AttachmentDetached
Number of storeys1 + basement
Weather locationParry Sound
Ventilation included?Included
HRV?Yes
Recovery % (sensible, at −25 °C)65%
Front facingSouth ASSUMED
Air tightness3 ACH50, ELA 620 cm² @ 10 Pa ASSUMED
Wind exposure / shieldingAIM-2 site 7, walls 3, flue 3
Internal shadingNone in this calculation
Occupants4
UnitsMetric (SI)
Heating: outdoor temperature-24 °C
Heating: indoor temperature22 °C
Mean soil temperature8 °C
Cooling: outdoor temperature28 °C
Cooling: indoor temperature24 °C
Latitude45.34°
Summer mean daily range14 °C or less
Above-grade walls2x6 @ 406, R22 batt + R5 ci (SB-12 A1, effective RSI 3.00) — U 0.333
Below-grade walls200 mm concrete, R20 interior full height (BasementHLR BCIN_1) — U 0.269
Floors—
CeilingsAttic, R60 blown — U 0.096
DoorsInsulated steel — U 1.4
WindowsDouble low-e argon, U 1.6 — U 1.6, SHGC 0.4
Skylights—
Attached documentsRoom-by-room results (this report)
NotesTeaching example
Calculations performed byStephen Gilbert, SBG Design Works
Address
BCIN

Results

ItemWBTU/hClause
Design heat loss, building (HLb)7,18724,5235.2.7
of which ventilation at building level (HLvairb)4831,6485.2.3.2
of which air leakage (HLairb)1,6005,4585.2.3.1
Sensible heat gain, Σ HGsr3,58412,2296.2.9
Nominal cooling capacity (CSCn = 1.3 × Σ HGsr)4,65915,8986.3.1
Cooling capacity window, minimum3,72812,7186.3.2
Cooling capacity window, maximum6,40921,8696.3.4 / 6.3.5
5.3.1MEETS Heating output 11254 W vs building loss 7187 W (≥ 100%) (157%)
6.3.2–6.3.5MEETS Cooling 5275 W vs window 3728–6409 W (113%)

Room-by-room heat loss (Clause 5)

RoomLevelΔTAbove-grade cond.Below-gradeLevel factorAir changeDuct/pipeVent.Total WBTU/h
Living roomM4694200.4176001,1183,814
Kitchen / diningM4695200.4178001,1303,854
Hall / stairM4615400.42900183625
Primary bedroomM4654400.4102006462,204
BathroomM4616100.43000192654
Bedroom 2M4623600.44400280954
Bedroom 3M4644100.482005231,784
Basement (unfinished)B463211,3530.6960002,6348,988
Σ rooms6,70422,875
+ ventilation, building level (5.2.7 note)4831,648
HLb7,18724,523

Room-by-room sensible heat gain (Clause 6)

RoomOpaqueGlass cond.SolarPeopleLights/appl.Air leakageVent.DuctTotal W
Living room734055114008360848
Kitchen / dining874056914095683801,838
Hall / stair38000002040
Primary bedroom4519204003150286
Bathroom173200002043
Bedroom 2209540014088
Bedroom 33516177003120243
Basement (unfinished)3710139002100198
Σ HGsr3,584

Table of inputs (Clause 7.1)

Design temperature differencesHeating 46 K; cooling 4 K (5.1, 6.1.1)
Building volume Vb (inside dimensions)584 m³
Gross floor area239 m² → lights/appliances 956 W (6.2.5)
Air leakage rates (AIM2.xls)Heating 0.1788 ACH; cooling 0.0329 ACH — run 2026-10-23T21:14:39 ASSUMED
Air leakage noteELA not measured: scaled from the tool's "Present (1961-)" type at the same volume (assumed) ASSUMED
AIM2.xls inputsStation Parry Sound; site 7, wall shielding 3, flue shielding 3; highest ceiling 3.34 m; Detached, One, Full foundation; supply 25 L/s, exhaust 25 L/s
Foundation F1 (BasementHLR.xls)BCIN_1 (#1); 12.2 × 9.8 m; height 2.44 m, depth 1.84 m; interior RSI 3.72, exterior RSI 0, slab RSI 0; soil 1, water table 2; windows 1.62 m² → 1,353 W
VentilationPVC 25 L/s; HRV sensible effectiveness 0.65; ATRE 0; into the central air system (not assigned to rooms)
SolarSolar0 per 6.2.2.1; latitude factor 1.20 on S/SE/SW; shaded glass treated as north

Prepared with the designer's own implementation of CSA F280-12; not software verified under F280-12 Clause 8. Spreadsheet-derived values are from CSA's AIM2.xls and BasementHLR.xls / SlabOnGradeHLR.xls run with the inputs above.